Browse Categories

White-Rodgers 668-601 Oil Burner Primary Control

<< Previous in White-Rodgers Next in White-Rodgers >>
Price: $56.06
Item Number: 17277
Manufacturer Name: White-Rodgers
Manufacturer Part No: 668-601

668-601 Specifics

668 SERIES KWIK-SENSOR CAD CELL RELAYS

Replaces Intermittent Ignition Kwik-Sensor CAD Cell Relays on Oil Burner Systems with 15, 30 or 45 Second Safety Timing. Certain Types have Unique Signal-Lite Feature which Glows Whenever Safety Lock-Out Occurs

FEATURES
• Grey metal enclosure.
• Line voltage safety switch eliminates burner run-on in event motor relay contacts weld closed.
• Solid state flame detection circuitry is not affected by vibration or high or low ambient temperatures. Suitable for use from – 40 to 150°F (– 40 to 66°C)
• Recycles upon momentary flame failure or power interruption.

SPECIFICATIONS
Input Voltage . . . . . . . . . . . . . . . . . . . . . . 120 VAC, 60 Hz
Control Voltage . . . . . . . . . . . . . . . . . . . . 24 VAC
Motor Relay Contacts Rating . . . . . . . . . . Full 10 FLA, 60 LRA, 120 VAC
Ignition Transformer Rating . . . . . . . . . . . 360 VA (3.0A)
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . 10” useable leads, mounts to 4 x 4” junction box