Honeywell VR8304P4504 Dual Valve Combination Gas Control
Item Number: VR8304P4504
Manufacturer Name: Honeywell
Manufacturer Part No: VR8304P4504/U
|
|
VR8304P4504/U Single Stage, 24 Vac, Step Opening Intermittent Pilot 3/4 x 3/4 Step rate 0.9" WC, Full Rate 3.5" WC
Overview
Combination gas control for use in 24 Vac gas-fired, intermittent pilot appliances with capacities from 30 to 415 cfh.
Features
- Controls include safety shutoff, manual valve, two automatic operators, pressure regulator and pilot adjustment.
- Use with S86F,H; S860D; S8600F,H; S8610 and S90A,B Control Modules.
- Compact size.
- Provide two automatic valves.
- Solenoid operated first automatic valve opens on thermostat call for heat; closes when call for heat ends.
- Diaphragm-operated second automatic valve opens under control of regulator; closes if gas or power supply is interrupted.
- Meet codes requiring dual safety shutoff.
- Natural to LP and LP to Natural conversion kits available for standard and slow opening gas valves.
- All adjustments, wiring connections and pilot outlet are accessible from top of control.
- Adjustable servo regulator effectively maintains almost constant gas output pressure under wide fluctuations in gas supply pressure.
- Compatible with ECO connector.
- ON-OFF lighting sequence.
Product Specifications
- Application: Single Stage
- Dimensions (in.): 5 3/8 in. high x 4 1/16 in. wide x 2 11/16 in. deep
- Dimensions (mm): 135 mm high x 104 mm wide x 69 mm deep
- Mounting: 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
- Frequency: 60 Hz
- Approvals, Underwriters Laboratories Inc.: UL Component Recognized MCCZ2.MH5323
- Approvals, CSA: CSA International: 112395
- Electrical Connections: 1/4 in. quick-connect male terminals
- Voltage: 24 Vac
- Operating Temperature Range (F): -40 F to +175 F
- Operating Temperature Range (C): -40 C to +79 C
- Body Pattern: Straight-through
- Opening Characteristics: Step Opening
- Pressure Ratings (psi): 1/2 psi
- Pressure Ratings (kPa): 3.5 kPa
- Inlet/Outlet Size (in.): 3/4 in. x 3/4 in.
- Pilot Gas Outlet: Compression fitting for 1/4 in. OD tubing
- Pressure Tapping: 1/8 in. NPT with plug
- Type of Fuel: Natural
- Capacity (kBtuh): At 1 in. wc p.d.-- 300,000 BTUh: 30,000 BTUh minimum: 415,000 BTUh maximum Natural Gas
- Pressure Regulator: Step
- Pressure Regulator Setpoint (in. wc): Step Setting: 0.9 in. WC non-adjustable; Full Rate: 3.5 in. wc
- Pressure Regulator Setpoint (kPa): Full Rate: 0.87 kPa; Step Setting: 0.22 kPa
- Ignition Type: Intermittent Pilot
|
Product Reviews